🇬🇧 - English Installation guide

Installation

  1.     Contact Outscale minimum two days in advance to schedule a time for testing the system prior to starting the installation

ada5d6b9-cc60-4510-bc26-31abba7c9a0d
  1.      The central unit (NOXone) must be connected to the door module (NOX CMU or CMO) via twisted pair bus cable. We recommend 4x2x0.6 PTS from Nexans or similar. The wiring is performed as a regular RS485 bus connection according to the Daisy-Chain principle, which means the cable must be routed from the central unit to the first door module, and then onto the second door module and so on.

b8244bfc-05b8-4f3c-9799-bb5b384d00b6

Contact Outscale to have the system tested on +45 69 69 13 23, on the time which you have previously scheduled.
After the testing is completed, please ensure to make a diagram of court names in relation to relays – this diagram should be forwarded to the owner of the courts who will in turn forward it to the Bookingmanager.

Connections in the central unit for light control

The relays in the center of the NOX correlates with the number of courts provided by the owner before purchase of the system

The relays can be used to turn on the lights and has a potential-free contact to control the lights.

Please note that the relays has a maximum switching capacity of 6A 250V and that extra relays might need to be added.

The courts are numbered 1-? from left to right

7fd9b84a-c6b8-4088-99ee-ccd57fe805e0

Terminal

11=Common

14=NO

12=NC

Connection of bus connection to door modules
(and potentially extra relay modules for lighting)

Terminal

Function

+

+15VDC bus supply

-

GND / Minus bus supply

A

RS 485 Data bus A (NOX protocol)

B

RS 485 Data bus B (NOX protocol)

Keypad installation

The keypad is connected to the NOX via the CMO-module. The CMO-module is installed accordingly to the specifications above.

The connection between the CMO and the Exread keypad reader must be made according to the drawing below. The recommended cable is a twisted pair. The cable used for the nox-bus can be used. Max length is 80m. but remeber EOL resistors in both ends on longer runs.

Montering-CMO-Exread

additional documentation

Linemap-NOXone-CMO-Teltonika-API-exread-ENG.pdf